Mars-Energo Reference standard meter Energomonitor - 3.3T1 is a specialized energy monitoring device used to track and measure energy consumption in industrial settings. This high-precision monitor provides real-time data, allowing users to analyze energy usage and optimize performance.
Functionality and options
Measurements :
Measured values
Testing of Meters :
EM 3.3T1 provides for performance and accuracy testing of electric energy meters (class 0.5 or less accurate). Test results acquired from up to 200 meters (up to 10 measurements per test) can be kept in the internal memory. With EmWorkNet, test results are loaded to a PC for viewing and managing. Test reports are generated automatically.
Testing of Current and Voltage Instruments transformers :
In this mode, EM 3.3T1 works as a comparator and provides for testing of voltage transformers (class up to 0.2) and 1A or 5A current transformers (class up to 0.25). The internal memory can store test results from up to 200 CTS and/or VT's. Automatic report generation and log management functions are available with Transformer Test software.
Measured values | Measurement ranges | Limits of permissible fundamental error | |
with Current Transformers Block (CTB) |
with High Precision Current Clamps |
||
RMS of AC voltage (U) |
1 to 360 V (UN = 60; 120; 240 V) |
0.1 %1 | |
RMS of AC current (I) | 5 mA to 60 A (CTB: In = 0,5; 5; 50 A) |
0.1 %2 | -- |
50 mA to 4500 A (Clamps: In = 10; 100; 1000; 300; 3000 A) |
- | 0.5 %3 | |
Phase angle between 1st harmonics of phase voltages | 0° to 360° | Absolute: 0.1° | |
Phase angle between 1st voltage and 1st current harmonics in the same phase | 0° to 360° | Absolute | |
0.2° | 0.5° | ||
Active power (Ð ), W | 0.01Un to 1.5Un, PF = 1 | Relative | |
0.1In ≤ I < 1.5In | 0.1 % | 0.5 % | |
0.01In ≤ I < 0.1In | 0.2 % | - | |
Reactive power (Q), Var |
0.05In Un to 1.5In ∙ 1.2Un |
Relative | |
PFR = 1 | 0.3 % | 1.0 % | |
PFR = 0.45L...0...–0.45C | 0.5 % | 2.0 % | |
Power Factor | –1.0 to +1.0 | Absolute | |
0.02 | 0.05 | ||
AC frequency | 45 to 70 Hz | Absolute: 0.01 % | |
Negative and zero sequence voltage ratios, % | 0 to 50 % | Absolute: 0.2 | |
Total Harmonic Distortion of voltage THDU and individual voltage harmonic ratios KU(n) (n from 2 to 40) |
0 to 49.9 % | Absolute: 0.05 % (THDU;KU(n) < 1.0) | |
Relative: 5.0 % (THDU;KU(n) ≥ 1,0) | |||
Total Harmonic Distortion of current THDI and individual current harmonic ratios KI(n) (n from 2 to 40) |
0 to 49.9 % | Absolute: 0.1 (THDI;KI(n) < 1.0) | |
Relative: 10.0 % (THDI;KI(n) ≥ 1,0) | |||
Ratio (modular) error of current and voltage instrument transformers δ |
1 to 100 % | Absolute: (0.02 + 0.02|δ|) % | |
Angle error of current and voltage instrument transformers ∆ | 0.1' to 180° | (1.0 + 0.1|∆|)' | |
Duration of voltage dips and swells | from 0.02 s | 0.02 s | |
Voltage dip depth | 10 to 100 % | Relative: 10.0 % | |
Voltage swell height (over-voltage factor) | 1.10 to 7.99 relative units | Relative: 2,0 % | |
Flicker short-term perceptibility | 0.25 to 10 | 5.0 % (∆U/U ≤ 20 %) |
Pulse input and output
Parameter | Input | Output |
Level | 5...15 V | 5 V |
Max. frequency | 36 kHz | 18 kHz |
Pulse duration | >10 μs | 10 ± 2 μs |
Constant | 1...999 999 999 pulses/(kW ∙ h) |
C = 14 400 000/(IN • UN) pls/(W • h) |
Technical data
Mains supply | 100...264 V, (50 ± 5) Hz |
Power consumption from mains | 20 VA, or less |
Consumed DC power (12 V from Power Adaptor or Rechargeable Power Supply) |
8 VA, or less |
Time of operation when powered from Rechargeable Power Supply |
minimum 2 h |
Safety requirements per IEC 61010-1 | |
Ingress protection rating | IP 40 |
Category of measurements | II or III |
Electric shock protection | Double insulation |
Overall dimensions (Length × Width × Height) |
Maximum 250 × 280 × 80 mmWeight |
Weight | 2.0 kg, or less |
Operating conditions | |
Ambient temperature | –20 to 55 °C |
Relative humidity | up to 90 % at 30 °C |
Atmospheric pressure | 70–106.7 kPa (537–800 mm Hg) |
Energomonitor Features:
Type | Reference Standard Meter |
Material | Cast Steel |
Accuracy Class | 0.05% |
Data Storage | 2 GB Internal Memory |
Communication Interfaces | USB, Ethernet |
Display Type | 12-inch Touchscreen |
Operating Temperature | 20°C To 50°C |
Power Supply | 100 -240 V AC |
Installation Type | Panel Mount |
Model Number | Energomonitor - 3.3T1 |
Calibration Interval | 24 Months |
Frequency | 50 - 60 Hz |
Protection Rating | IP54 |
Application | Industrial And Commercial Settings |
Sampling Rate | 1 KHz |
Software Compatibility | Windows Based Software |
Additional Features | Remote Monitoring, Energy Analysis |
Supplier | Myriad Industrial Solutions LLP |
Origin | India |