PW466i protective relay test set is an economic model with 6 current channels and 6 voltage channels, capable of automatic testing different kinds of protection relays, such as distance, overcurrent, frequency, differential relay easily without changing cable connection. This device supports multi-phase testing and is capable of handling complex relay schemes. Its user-friendly interface and powerful diagnostic tools allow engineers to simulate various fault conditions and assess relay responses accurately.
Product Features :
Inâ€Built Analog Monitoring & Recording Unit:
Real Time Outputs Display :
IEC 61850 Function:
Application:
Voltage generators :
Setting range:
6â€phase ac(Lâ€N) | 6×0~150V |
1â€phase ac(Lâ€L) | 1×0~300V |
dc (Lâ€N) | 6×±0~150V |
dc (Lâ€L) | 1×±0~300V |
Power:
6â€phase ac(Lâ€N) | 6×30VA at 150V |
3â€phase ac(Lâ€N) | 3×60VA at 150V |
1â€phase ac(Lâ€L) |
1×100VA at 300V |
dc (Lâ€N) | 6×40W at 150 V |
Accuracy | error < 0.08% rd.+0.02% rg. guar. error < 0.04% rd.+0.01% rg. typ. |
Ranges | 150V |
Resolution | 5mV for 150Vac |
Distortion | < 0.05% typ. (< 0.1% guar.) |
Setting range:
6â€phase ac(Lâ€N) | 6×0~20A |
3â€phase ac(2Lâ€N) | 3×0~40A |
1â€phase ac(6Lâ€N) | 1×0~120A |
dc (Lâ€N) | 6×±0~20A |
dc (6Lâ€N) | 1×±0~120A |
Power:
6â€phase ac(Lâ€N) | 6×180VA typ., at 20A 6×150VA guar., at 15A |
3â€phase ac(2Lâ€N) | 3×320VA typ., at 40A 3×240VA guar., at 30A |
1â€phase ac(6Lâ€N) | 1×600VA typ., at 120A 1×450VA guar., at 90A |
1â€phase ac(Lâ€L) | 1×450VA typ., at 30A |
Max compliance voltage(Lâ€N)(Lâ€L) | 15Vpk/30Vpk |
dc (Lâ€N) | 6×100W at 10A |
dc (6Lâ€N) | 1×480W at 60A |
Accuracy | error < 0.15% rd.+0.05% rg. guar. error < 0.08% rd.+0.02% rg. typ. |
Ranges | 20A or 40A |
Resolution | 1mA |
Distortion | < 0.05% typ. (< 0.1% guar.) |
Frequency :
Sine signal | DC, 0.001Hz~1000Hz |
Transient signal | DC~10.0kHz |
Accuracy | ±0.3ppm |
Resolution | 0.001Hz |
Phase :
Angle range | â€360°~+360° |
Accuracy | <0.05° typ., <0.1° guar.. at 50/60Hz |
Resolution | ±0.001° |
Auxialiary DC Supply :
Voltage range | 0~300V |
Power | 88W at 110V, 176W at 220V, 120W at 300V |
Accuracy | error < 0.1% rg. typ. (<0.5% rg. guar.) |
Binary inputs
Number | 8 |
Input characteristics | 0~400Vdc/ac peak threshold or potential free |
Time resolution | 100μs |
Max. measuring time | Infinite |
Debounce/Deglitch time | 0~25ms |
Counting function | < 3kHz at pulse width>150μs |
Binary output, relay :
Number | 4 |
Type | Potential free relay contacts, software controlled |
Break capacity ac | Vmax: 300Vac /Imax: 8A /Pmax: 2000VA |
Break capacity dc | Vmax: 300Vdc /Imax:8A/Pmax: 150W |
Inâ€built monitoring and recording :
Monitoring | currents and voltage outputs |
Recording | analog outputs, binary inputs/outputs status |
Mode | real time monitoring, no external wiring is required |
Recording length | 16s |
Power Supply :
Nominal input voltage | 110~240Vac |
Permissible input voltage | 90~260Vac |
Nominal frequency | 50/60Hz |
Permissible frequency | 45~65Hz |
Environmental conditions :
Operation temperature | 0~+50°C |
Storage temperature | â€25~+70°C |
Relative humidity | 5~95% non †condensing |
EMC(E&I) | EN/IEC 61326â€1 EN/IEC 61000â€3â€2/3 EN/IEC61000â€4â€2/3/4/5/6/8/11/18 |
Environment | EN/IEC 60068â€2â€1/2/3/6/27 |
Safety | EN/IEC 61010â€1/1â€12/2â€030 EN/IEC 60255â€25/27 |
Others | FCC Part 15:Sub B ECSâ€001:2006 LVD EU |
Others :
PC connection | Ethernet,10M/100M |
GPS interface | DB9/TTL |
Ground Socket(earth) | 4mm banana socket, front side |
Weight | 20kg |
Dimensions (WxHxD) | 360mm ×157mm×367mm |
Applications: Ideal for professionals in power system protection, relay testing, and substation automation.
Testing System Features:
Product Code | PW466i |
Type | Relay Testing System |
Material | Mild Steel |
Model Name | PW466i |
Output Current | Up To 10 A |
User Interface | 10.1-inch LCD Touchscreen |
Finish | Coated |
Communication Protocols | Modbus, DNP3, And Ethernet |
Operating Temperature | -20°C To 60°C |
Weight | 5 Kg |
Test Modes | Automatic, Manual |
User Memory | Up To 100 Test Configurations |
Battery Backup | Integrated UPS Feature |
Protection Ratings | IP54 Rated |
Used For | Training, System Verification |
Calibration Certainty | 0.05% Accuracy |
Software Suite | Includes Reporting And Analysis Tools |
Supply By | Myriad Industrial Solutions LLP |
Country Of Origin | India |